Post Offer Free
Shenzhen Jendia Electronics Co.,Ltd  

Gold Index: 9420

You are here: home  > 3 Phase Online UPS  > OEM energy saving UPS 3 phase Online ups modular design 10KVA - 300KVA Output power factor 0.9

OEM energy saving UPS 3 phase Online ups modular design 10KVA - 300KVA Output power factor 0.9 

Place of Origin: Zhejiang, China (Mainland) 
inquire
Add to My Favorites
HiSupplier Escrow
Share |

Product Detail

Model No.: MPS9335C


OEM energy

OEM energy saving UPS 3 phase Online ups modular design 10KVA - 300KVA Output power factor 0.9

 

Specifications

 
Output power factor: 0.9
LCD display
220V(single phase), 380/400/415V(three phase)
Modular UPS
12 Language

 

 

Single and three phase Modular UPS MPS9335C 10KVA-300KVA

 

Key Features


1. Superior energy saving and environment-friendly:
Efficiency > 96% at 50%-75%rated load, and > 95% at
25% rated load; Input PF >0.99,input THDi<3%
2. Superior capability of powering load:
Output PF is 0.9, no need ofpower deration with load of
leading or lagging PF
3. Easy-to-install:
Top or bottom cabling, no needof input cabling cabinet.
4. Easy-to-maintain:
Full front access, UPS, failedpart can be replaced shortly
5. Easy-to-modify:
The number of battery cellscan be configured flexibly, so
the original batteries can beused when modifying the
legacy system; moreover,the battery cell can be replaced
in time when it fails withoutinterrupting the normal
operation of UPS.
6. 6-inch extra large LCD that can display 12language(Chinese,English,Russian,Spanish,French and soon )

UPS Modules

 

Application:


ApplicationIDC(Internet Data Center), computing center,
ISP (Internet Service Provider ),Telecom,Finance bank
and securities, Tax, hospital system, industrial automation,
precision equipment, etc.

 

Technical Specifications of Modular UPS, MPS9335 10-300KVA

Model

MPS9335 10-300KVA
Capacity 10-300KVA
Main input  
Input voltage 380V/400V/415AC(Optional South America 208v)
Input Frequency Range 50/60Hz
Power Factor Full load>0.99 ,Half load >0. 98
THDi THDi <3%
Input power soft-start fantion 5-30s settable
Input Voltage Ranges 228V-476V-20%- +25% Full load linear derating at -25% --40%; can take 70% load at -40%
Frequency Range 40-70Hz
Battery  
Battery Voltage ±240VDC(Default),12V Battery30-40pcs can be choose
Charge Voltage accuracy ± 1%
Bypass  
Bypass Input voltage 380/400/415VAC 3-phase 4-wire
Voltage Ranges Default value is -20%-+15%, -40%, -30%, -10% - +10%, otherranges can be set via software
Overload Capacity 150%,long term operation,150%<load<180%,more than 1hour ,load>1000% 100ms
Output  
Inverter Output Voltage 380/400/415VAC 3-phase 4-wire
Voltage Accuracy ± 0.5%(balancedload), ± 1% (unbalanced load)
THDi THD<1%(linearload), THD<3%(nonlinear load)
bigPhoto
 Mr. Robert

Tel: 86-755-2331354
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Shenzhen Jendia Electronics Co.,Ltd [China (Mainland)]


Business Type:Manufacturer
City: Shenzhen
Province/State: Guangdong
Country/Region: China (Mainland)

You May Like: