Shenzhen Jendia Electronics Co.,Ltd
|
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Place of Origin: | China (Mainland) | Brand Name: | OEM | Model Number: | SLP |
Phase: | Standby/line Interactive | Protection: | Lightning | Weight: | 18-28KG |
Output Voltage: | 220VA | Type: | Standby | Application: | Computer |
LCD LED option
output voltage can setting at 220V,230V,240V
EPO,ECO
work with generator selection
from 750VA-3KVA
LCD LED option
output voltage can setting at 220V,230V,240V
EPO,ECO
work with generator selection
from 750VA-3KVA
Product | Requirements | Model 1 | Model 2 | Model 3 | Model 4 | Model 5 |
Power (VA) | SLP-750VA | SLP-1000VA | SLP-1500VA | SLP-2000VA | SLP-3000VA | |
Input | Voltage | 220/230/240VAC ±20%(176-288±4V) | ||||
Frequency | 60/50Hz +/-10% | |||||
Output | Voltage(AVR) | 220/230/240VAC±10% Boost:114% of Vin, Bulk:88 % of Vin | ||||
Voltage (Inverter Mode) | 220/230/240VAC ± 5% (+5% ,-10% after Low Battery Warning) | |||||
Capacity | 750VA/500W | 1000VA/700W | 1500VA/1050W | 2000VA/1340W | 3000VA/2100W | |
Frequency (Inverter Mode) | 60/50Hz ±+/- 0.1 Hz | |||||
Load Power Factor | 0.7 | |||||
DC Component | 10sec average < 0.1% of rms value of output voltage | |||||
Transfer Time | 2-4MS typical,6MS max |
Break out for 6-msec.max. Generator mode for 10 msec.max |
||||
Waveform | Sine wave | |||||
Communication Interface | USB, RS232,Dry Contact ,SNMP(optional) | |||||
Protection | Spike & Surge Suppression | yes | ||||
High/Low Voltage Protection | Switch to Bat. O / P when Mains over regulation range | |||||
Over load /short Circuit | Fuse & current limited for both Mains and Battery modes | |||||
Function | Cool start | Cool start computer even there is no main power | ||||
EPO function |
Short circuit the EPO, the UPS will shut down output immediately in both line mode or battery mode. |
|||||
LED's display | UPS on, battery level, general failure, AVR | |||||
Automatic recharge | Automatic recharge even UPS is off | |||||
Battery | Type | Lead-Acid maintenance-free | ||||
Dc Bus | 24V | 24V | 48v | 96V | ||
Number | 7AH*2PCS | 9AH*2PCS | 9AH*4PCS | 4.5AH*8PCS | ||
Charge current | 3A typical | |||||
Recharge time | Internal battery modules will recharge <3 hours to 90% usable capacity nominal line after full load discharge. | |||||
Back up time(at 100% PFC or SPS load ) | >5mins | >5mins | >5mins | >5mins | >5mins | |
Efficiency | AC-AC | >95 % for normal mode, 92% for boost and buck mode | ||||
DC-AC | >85% | |||||
Acoustic | Noise level | < 55dBA | ||||
Environmental | Altitude | 0-1500 meters | ||||
Storage Temperature | 0 to 25°C (recommended for batteries). | |||||
Operating Temperature | 0-40 DegreeC | |||||
Humidity | 20% to 80% | |||||
Power Outlets | No. and types | IEC320, 4pcs | IEC320, 6pcs | IEC320, 8pcs | ||
Physical | N.W.(KGs) | 15.2 | 16 | 21 | 21.8 | 26.4 |
G.W.(KGs) | 17.2 | 18 | 23 | 23.5 | 28.5 | |
Product Dimensions (mm) | 380*440*88 | 480*440*88 | 570*440*88 | |||
Package Dimensions (mm) | 552*550*210 | 652*550*210 | 742*550*210 |